| | 1. Residential construction, remodeling and renovation. | Except as provided in this section, during the construction, | remodeling or renovation of a multifamily residential building, a | person may not install electric space heating equipment as the | primary heating system if that construction, remodeling or | renovation is funded in whole or in part by public funds, | guarantees or bond proceeds. For purposes of this section, | "multifamily residential building" means a structure with more | than one dwelling unit. |
|
| | 2. Waiver. After written petition from a building owner, the | commissioner commission shall grant a waiver from subsection 1 if | the building design conforms to the residential standards set | forth in subsection 3 or 4. A waiver granted by the commissioner | commission under this subsection must be in writing and state the | commissioner's commission's reason for granting the waiver. |
|
| | 3. Residential standards; electric heat. If the commissioner | commission grants a waiver under subsection 2, the building owner | shall renovate the building or construct a new building so that | the entire building conforms to the minimum energy efficiency | standards established in this section. If a waiver is granted | under subsection 2 for a building to be remodeled or a building | that receives an addition, only the remodeled portion of the | building or the addition must conform to the following minimum | energy efficiency standards. |
|
| A. All ceilings that face an outdoor or unheated space must | be insulated to an R-value of 57 or greater. |
|
| B. All walls that face an outdoor or unheated space must be | insulated to an R-value of 38 or greater. |
|
| C. All floors over unheated spaces must be insulated to an | R-value of 25 or greater. |
|
| D. Slab-on-grade floors must have perimeter insulation of | either: |
|
| (1) R-15 when the insulation extends downward from the | top of the slab to the design frost line; or |
|
| (2) R-15 when the insulation extends around the | perimeter and horizontally or diagonally beneath or | away from the slab for a distance equivalent to the | depth of the frost line. |
|
|