| | | E. For natural gas-fired and propane-fired steam boilers, a | | minimum efficiency level of 82%; and |
|
| | | F. For oil-fired steam boilers, a minimum efficiency level | | of 82%. |
|
| | | The commission may adopt rules to exempt compliance with furnace | | or boiler standards at any building, site or location if | | compliance with those standards would conflict with any local | | zoning ordinance, building or plumbing code or other rule | | regarding installation and venting of boilers or furnaces. |
|
| | | 9. Furnace air handlers must have an efficiency ratio of 2.0 | | percent or less, except that air handlers for oil-fired furnaces | | with a capacity of less than 94,000 BTUs per hour must have an | | efficiency ratio of 2.3 percent or less. |
|
| | | 10. High-intensity discharge lamp ballasts may not be | | designed or marketed to operate a mercury vapor lamp. |
|
| | | 11. Illuminated exit signs must have an input power demand of | | 5 watts or less per illuminated face. |
|
| | | 12. Large packaged air-conditioning equipment must meet or | | exceed the following minimum energy efficiency ratios: |
|
| | | A. For air conditioning without an integrated heating | | component or with electric resistance heating integrated | | into the unit, a minimum energy efficiency ratio of 10.0; |
|
| | | B. For air conditioning with heating other than electric | | resistance integrated into the unit, a minimum energy | | efficiency ratio of 9.8; |
|
| | | C. For air-conditioning heat pumps without an integrated | | heating component or with electric resistance heating | | integrated into the unit, a minimum energy efficiency ratio | | of 9.5; and |
|
| | | D. For air-conditioning heat pump equipment with heating | | other than electric resistance integrated into the unit, a | | minimum energy efficiency ratio of 9.3. |
|
| | | Large packaged air-conditioning heat pumps must meet a minimum | | coefficient of performance in the heating mode of 3.2. |
|
| | | 13. Low-voltage dry-type distribution transformers must meet | | or exceed the Class 1 efficiency levels for low-voltage | | distribution transformers specified in Table 4-2 of the "Guide | | for Determining Energy Efficiency for Distribution Transformers" |
|
|